| Number of analog inputs |
2 |
| Total number of channels (module) |
2 |
| Signal type |
Electricity |
| Signal type (current) |
DC 4 … 20 mA |
| Sensor connection |
2 x (2-wire, 3-wire) |
| Input filter frequency (analog) |
50 Hz |
| Input voltage (max.) |
24 V |
| Input voltage (note) |
Non-linear, overload protected U = 1.2 V + 160 Ω x I meas |
| Signal characteristic |
Single-ended |
| Resolution [bit] |
15 Bit |
| Input resistance (max.) |
220 Ω |
| Data width |
2 x 16-bit data; 2 x 8-bit control/status (optional) |
| Overvoltage protection |
30 V, reverse polarity protected |
| Noise rejection at sampling frequency |
-100 dB |
| Noise rejection above sampling frequency |
-40 dB |
| Conversion time (typ.) |
80 ms |
| Measurement error (reference temperature) |
25 °C |
| Measurement error – deviation (max.) from the upper-range value |
0.1 % |
| Temperature error (max.) of the upper-range value |
0.01 %/K |
| Supply voltage (system) |
DC 5 V; via data contacts |
| Power consumption (5 V system supply) |
75 mA |
| Supply voltage (field) |
DC 24 V (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
| Isolation |
500 V system/field |
| Number of incoming power jumper contacts |
2 |
| Number of outgoing power jumper contacts |
2 |