Number of analog inputs |
2 |
Total number of channels (module) |
2 |
Signal type |
Electricity |
Signal type (current) |
DC 4 … 20 mA |
Sensor connection |
2 x (2-wire, 3-wire) |
Input filter frequency (analog) |
50 Hz |
Input voltage (max.) |
24 V |
Input voltage (note) |
Non-linear, overload protected U = 1.2 V + 160 Ω x I meas |
Signal characteristic |
Single-ended |
Resolution [bit] |
15 Bit |
Input resistance (max.) |
220 Ω |
Data width |
2 x 16-bit data; 2 x 8-bit control/status (optional) |
Overvoltage protection |
30 V, reverse polarity protected |
Noise rejection at sampling frequency |
-100 dB |
Noise rejection above sampling frequency |
-40 dB |
Conversion time (typ.) |
80 ms |
Measurement error (reference temperature) |
25 °C |
Measurement error – deviation (max.) from the upper-range value |
0.1 % |
Temperature error (max.) of the upper-range value |
0.01 %/K |
Supply voltage (system) |
DC 5 V; via data contacts |
Power consumption (5 V system supply) |
75 mA |
Supply voltage (field) |
DC 24 V (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
Isolation |
500 V system/field |
Number of incoming power jumper contacts |
2 |
Number of outgoing power jumper contacts |
2 |