Technical data | 0.1 % of span ± 1 LSD |
Temperature Stability | 0.01 % of span per °C |
Input Signal Failure | Fail-safe output value: Achieved when burnout is detected. Value depends on configuration. For thermocouple and mV input detected by any lead break: Upscale burnout For RTD: Burnout detected by any lead break Current or voltage input: Burnout set by open circuit detection |
Input Impedance | Voltage impedance: 47 Kohms Current input: 4.7 ohms All others: 100 Mohms |
Input Sampling Rate | Four samples per second |
Input Filter | Digital filter configurable from front panel 0.0 (Off), from 0.5 seconds to 100.0 seconds in 0.5 seconds increment |
Input Resolution | 14 bits approximately, always four times better than display resolution |
Input Isolation | Universal input isolated at 2500 V from all outputs except SSR and from power supply |
Stray Rejection | Common mode rejection: > 120 dB at 50/60 Hz Serial mode rejection: > 500% of span at 50/60 Hz |
Approvals | UL recognized to US & Canadian standards FM approval on the UDC1200 limit model Product design to meet CE MARK requirement |
Control Output Type | Type available: Output 1/2/3: DC, Electromechanical relay, SSR drive (open collector) DC linear output: 0-20 mA, 4-20 mA, 0-5 V, 0-10 V Accuracy: ± 0.25 % (250 ohms for mA, 2 Kohms for voltage) Resolution: 80 bits in 250 ms (10 bits in 1 second typical > 10 bits in > 1 second) Load impedance: 500 ohms maximum for current output, 500 ohms minimum for voltage output Isolation: Isolated 2500 V from all other inputs and outputs Range selection method: Front panel code setting Temperature stability: 0.01 % / °C Electromechanical relay: SPDT contact Resistive load: 2 A at 120 V or 240 V Life time: > 500000 operations at rated voltage/current SSR drive/TTL: Drive capability: SSR > 10 Vdc into 250 ohms minimum Isolation: Not isolated from input and other SSR output |
Alarms | Maximum number of alarms: 2 soft alarms setpoint + 1 loop alarm Alarm inhibit available on power up and setpoint switching Alarm output: Up to two relays or SSR output on outputs 2 and 3 Types: PV high or low, band, deviation high or low, loop Combination alarms: Logical “OR”, “AND” or hysteresis of alarms available to individual hardware output |
Loop Control | Automatic tuning type: Pre-tune and self-tune Proportional bands: 0 (inactive), 0.5 % to 999.9 % of input span with 0.1% increments. Two proportional bands available for duplex mode Reset: Off or from 1sec. to 99 min 59 sec. Rate: From 0 sec. to 99 min 59 sec. Manual reset: from 0 to 100 % of output (single output), from –100 % to 100 % of output (dual output) Deadband: ± 20 of PB1 + PB2 ON/OFF hysteresis: 0.1% to 10.0 % of input span Auto/manual mode: Front key selectable with bumpless transfer between automatic and manual mode Cycle times: Up to two cycle times available for time duplex control Selection: 0.5, 1, 2, 4, 8, 16, 32, 64, 128, 256, or 512 seconds Setpoint ramp: From 1 to 9999 engineering units per hour |
Retransmission Output | Any output can be selected to retransmit the process value or setpoint as a linear (current or voltage) output |
Digital Input (optional) | On contact the digital input will switch between SP1/SP2 or Auto/Manual or DC100L Remote Reset |
Communication Interface | RS485 – ASCII or Modbus RTU (selectable from the menu) Baud rate: 1200, 2400, 4800, 9600 or 19200 baud Link characteristics: 32 drops maximum, ASCII or Modbus protocols, two wires |
Mounting | Plug-in with pre-assembled mounting fixture |
Wiring Connection | Screw terminals on the rear of the case (combination head) |
Power Consumption | 4 W |
Physical (UDC1200) | Weight: 210 grams maximum Height: 48 mm / 1.89 in Width: 48 mm / 1.89 in Depth: 110 mm / 4.33 in Cut out: 45 mm x 45 mm / 1.77 in x 1.77 in |
Physical (UDC1700) | Weight: 250 grams maximum Height: 96 mm / 3.78 in Width: 48 mm / 1.89 in Depth: 100 mm / 3.94 in Cut out: 45 mm x 92 mm / 1.77 in x 3.62 in |
Environmental | EMI Susceptibility: Designed to meet EN55101 EMI Emission: Designed to meet EN55022 Safety Considerations: Designed to comply with IEC1010-1as far as applicable |
Front Panel Sealing | NEMA 3 / IP66 |