| Number of analog inputs |
2 |
| Total number of channels (module) |
2 |
| Type of signal |
Current |
| Type of signal current |
DC 4 … 20 mA |
| Sensor connection |
2 x (2-conductor, 3-conductor) |
| Input voltage (max.) |
10V |
| Signal characteristic |
Single-ended |
| Resolution [bit] |
12 Bit |
| Input resistance max. |
220 Ω |
| Bit width |
2 x 16-bit data; 2 x 8-bit control/status (optional) |
| Conversion time (typ. ≤) |
2 ms |
| Messfehler, Bezugstemperatur |
25 °C |
| Messfehler, Abweichung max. vom Messbereichsendwert |
0.2 % |
| Temperaturfehler max. vom Messbereichsendwert |
0.01 %/K |
| System supply voltage |
DC 5 V); via data contacts |
| Current consumption, system supply (5 V) |
75 mA |
| System and sensor supply voltage |
) |
| Field supply voltage |
DC 24 V(-25 … +30 %); über Leistungskontakte (Einspeisung über Messerkontakt; Weiterleitung über Federkontakt) |
| Isolation |
500 V system/supply |
| Number of incoming power jumper contacts |
2 |
| Number of outgoing power jumper contacts |
2 |