Number of analog inputs |
2 |
Total number of channels (module) |
2 |
Type of signal |
Current |
Type of signal current |
DC 4 … 20 mA |
Sensor connection |
2 x (2-conductor, 3-conductor) |
Input voltage (max.) |
10V |
Signal characteristic |
Single-ended |
Resolution [bit] |
12 Bit |
Input resistance max. |
220 Ω |
Bit width |
2 x 16-bit data; 2 x 8-bit control/status (optional) |
Conversion time (typ. ≤) |
2 ms |
Messfehler, Bezugstemperatur |
25 °C |
Messfehler, Abweichung max. vom Messbereichsendwert |
0.2 % |
Temperaturfehler max. vom Messbereichsendwert |
0.01 %/K |
System supply voltage |
DC 5 V); via data contacts |
Current consumption, system supply (5 V) |
75 mA |
System and sensor supply voltage |
) |
Field supply voltage |
DC 24 V(-25 … +30 %); über Leistungskontakte (Einspeisung über Messerkontakt; Weiterleitung über Federkontakt) |
Isolation |
500 V system/supply |
Number of incoming power jumper contacts |
2 |
Number of outgoing power jumper contacts |
2 |