Number of digital outputs |
2 |
Total number of channels (module) |
2 |
Actuator connection |
2 x (1-conductor) |
Output switching design |
2 make contacts relay |
Output characteristic |
potential-free |
Switching frequency max. |
0.5 Hz; Nennlast |
Switching frequency max. |
0.5 Hz |
Load type of the switching frequency |
Nennlast |
Switching voltage (max.) |
AC 250 V, DC 30 V V |
Switching current max. |
2 A |
Switching voltage (min.) |
5 V |
Switching current (min.) |
10 mA |
Switching power |
500 VA / 60 W; cos ϕ max. = 0.4; L/R max. = 7 ms |
Pull-in time (max.) |
10 ms |
Drop-out time (max.) |
10 ms |
Bounce time (typ.) |
1.2 ms |
Schaltspiele elektrisch min. (bei max. ohmscher Last) |
3 x 105 |
Schaltspiele mechanisch min. (bei max. ohmscher Last) |
20 x 106 |
Max output data width (internal) |
2 Bit |
System supply voltage |
DC 5 V); via data contacts |
Current consumption, system supply (5 V) |
100 mA |
System and sensor supply voltage |
) |
Isolation field – system |
1500 VAC (1 min) |
Indicators |
LED (A, C) green: Status relay 1, relay 2 |
Number of incoming power jumper contacts |
1 |
Number of outgoing power jumper contacts |
1 |
Current carrying capacity of the power jumper contacts |
10 A |